Launching the ecoMeter Probe Configuration from within ecoMeter Administrator Fails with a "Not Found" Error

Document ID : KB000074472
Last Modified Date : 21/03/2018
Show Technical Document Details
Issue:
In the ecoMeter administrator portlet after selecting the ecoMeter probe and clicking the "Probe Config" button, a page is then launched in
  a new tab (where the Template Editor and probe config page would normally appear) that shows only a "Not Found" error message.

ex.
ecoMeter Administrator - Click Probe Config
 

ecoMeter Administrator - Probe Config - Not Found
Environment:
ecometer_monitor 5.01
ecometer_admin 5.01
ecometer_3rdpartylibs 5.01
Resolution:
In the UMP's wasp folder
  • Edit: \Nimsoft\probes\service\wasp\conf\ecometerGlobal.properties
  • Add: UIM_ADMINCONSOLE_URL=http://<primaryHub>:<port>
Note: Enter the IP and port where the Admin Console is located, typically the primary hub and port 80

example (If a port ':port' is not entered the url defaults to port 80 or 443 if https is specified)
ecoMeter Administrator - ecometerGlobal.Properties    
  • Cold start ump's wasp probe

Configure the wasp on the primary hub
 
adminconsoleapp ~~> Path (change to /adminconsole) 
 
Admin Console - wasp - webapp - adminconsoleapp - change path
 
  • Cold start the adminconsole wasp probe on the primary hub